G
Guest

Method Statement: Installation of Electromagnetic or Ultrasonic Flow Meters on Water Networks inspection and test plan example.

Inspection and Test Plan for Method Statement: Installation of Electromagnetic or Ultrasonic Flow Meters on Water Networks

AI-assisted inspection and test plan connected to a method statement, with PDF and Excel export.

Published 20 Oct 2026 Rev. 00 3 views
About this ITP: This ITP defines inspections, tests, responsibilities, and records for installing and commissioning electromagnetic or ultrasonic flow meters on water pipelines.

More than a static template

Unlike a downloadable Word or PDF template, this ITP is an AI-assisted editable starting point directly connected to its method statement. Every inspection activity, hold point, and acceptance criterion is structured and ready to adapt to your project.

  • AI-assisted customization — Tailor inspection activities and acceptance criteria to your specific project scope.
  • Linked method statement — This ITP is connected to the corresponding method statement describing the work sequence.
  • Multiple export formats — Download as a formatted PDF or editable Excel spreadsheet.
  • Editable starting point, not a final document — Review and verify all content against your project specifications and standards before use.

What you can customize

When you save this ITP to your account, every inspection row becomes editable. You can add, remove, or modify:

  • Inspection activity — Description of what is being inspected.
  • Inspection type — Hold point (H), Witness point (W), Review (R), or Monitor (M).
  • Responsibility — Contractor, subcontractor, engineer, or client.
  • Frequency — How often the inspection occurs.
  • Acceptance criteria — Referenced standard or specification requirement.
  • Records — Forms, test reports, or checklists required as evidence.

Why this ITP is used

To provide structured inspection and testing control, ensuring installation meets technical and HSE requirements with traceable records.

Who uses this inspection and test plan

QA/QC inspectors, site engineers, instrument technicians, and the Employer’s Representative for witnessing and acceptance.

When this ITP is prepared and submitted

From pre-installation through commissioning and handover for each meter installation.

Who receives or approves this ITP

Engineer/Employer’s Representative for review, witnessing, and approval.

Inspection scope

Permits and isolation, straight-run verification, materials, flange assembly and torque, earthing, electrical tests, hydro/leak testing, zeroing/diagnostics, calibration verification, and loop checks.

Typical hold, witness, and review points

Hold: straight-run confirmation, hydro/leak test, calibration verification. Witness: earthing continuity, torqueing, loop checks.

Typical inspection records

Material certificates, torque logs, IR/continuity sheets, hydrotest report, vendor verification report, loop check sheets, configuration data, as-built photos.

Important approval note

This ITP is an AI-assisted editable starting point, not a pre-approved document. Before use on any project, all inspection activities, hold points, and acceptance criteria must be reviewed and approved by the relevant parties (superintendent, principal contractor, or client representative) in accordance with your contract and project quality plan.

Always verify acceptance criteria against your applicable drawings, specifications, and regulatory requirements. Hold points must be confirmed with the relevant authority before work proceeds past that point.

Inspection and test plan

Activity Inspection / Test Acceptance Criteria Responsibility Record
Permits and isolation (LOTO) Verify permits issued, valves closed/locked, zero pressure confirmed LOTO applied and recorded; vent shows 0 barg HSE Officer / Site Engineer PTW & LOTO records
Straight-run measurement and location confirmation Measure upstream/downstream lengths; check disturbances Meets manufacturer/project minimum D requirements Site Engineer / QA/QC Straight-run sheet; photos
Material verification Check meter tag, size, rating; certificates for potable compliance Correct model/tag; certificates present and valid QA/QC Inspector Material inspection report
Flange face/gasket/bolt inspection Visual examination pre-assembly Clean undamaged faces; correct gasket and bolts QA/QC + Mechanical Supervisor Fit-up checklist
Meter orientation and arrow check Confirm flow arrow and electrode orientation (mag) Arrow with flow; electrodes horizontal QA/QC / Site Engineer Inspection record; photo
Bolting and torque Torque in star pattern; verify with calibrated wrench Torque per vendor/flange table; uniform gasket compression Mechanical Supervisor / QA/QC Torque log
Earthing/grounding (mag meters) Continuity from meter/rings to earth bar Resistance ≤1 Ω [Verify per project] Instrumentation Supervisor / QA/QC Continuity test sheet
Cabling IR and continuity 500 Vdc IR test; continuity and polarity IR ≥1 MΩ; polarity/shield termination correct Electrician / QA/QC Cable test results
Hydrostatic/leak test Pressurize and hold per project spec No visible leaks; hold per spec; acceptable pressure drop [Verify] Mechanical Supervisor / QA/QC / Engineer Pressure test report
Zeroing and diagnostics Run vendor zero and diagnostics routines Zero within vendor limit; diagnostics pass Instrument Tech / QA/QC Diagnostic report
Calibration verification Reference comparison or built-in verification Within stated accuracy class [Verify] QA/QC / Vendor Rep (if specified) Verification report; certificates
Loop checks to SCADA/RTU Simulate 0/25/50/75/100% Readback within ±0.5% span; correct scaling/units Instrument Tech / SCADA Engineer Loop check sheets
Final acceptance Documentation, labeling, housekeeping All records complete; punch list cleared Engineer / QA/QC / Client Final acceptance form

This table is a read-only public reference. Download the PDF or Excel version, or customize this ITP to edit it for your project.

Frequently asked questions

Yes, unless waived in writing by the Engineer. The test pressure and duration must follow project specifications or relevant AWWA/ISO standards.

Comparison to a reference method or vendor verification that confirms meter performance within the project’s specified accuracy class, documented with a signed report.

The Contractor’s QA/QC raises the inspection request; the Engineer/Employer’s Representative witnesses and signs the hold point clearance per the ITP.

Related method statement

This Inspection and Test Plan is associated with the Method Statement: Installation of Electromagnetic or Ultrasonic Flow Meters on Water Networks method statement, which describes the step-by-step construction sequence, resources, materials, equipment, safety controls, and environmental controls for this activity.

View the Method Statement: Installation of Electromagnetic or Ultrasonic Flow Meters on Water Networks method statement →

Related resources