G
Guest

Method Statement – Installation of Fire-Rated Doors and Frames with Certified Hardware, Smoke/Intumescent Seals, Interfaces and Testing – Method Statement
Method Statement – Installation of Fire-Rated Doors and Frames with Certified Hardware, Smoke/Intumescent Seals, Interfaces and Testing method statement and inspection test plan example.

Method Statement – Installation of Fire-Rated Doors and Frames with Certified Hardware, Smoke/Intumescent Seals, Interfaces and Testing – Method Statement

AI-assisted method statement with matching ITP, PDF download, and Excel export.

Published 16 Jun 2026 Rev. 00 1 views
About this method statement: This method statement details installation of certified fire-rated doors, frames, and hardware. It includes smoke/intumescent seals, perimeter fire-stopping, QA/ITP hold points, and functional testing for AHJ compliance.

More than a static template

Unlike a downloadable Word or PDF template, this method statement is an AI-assisted editable starting point connected directly to a matching Inspection and Test Plan. Every section is structured, project-adaptable, and ready to export.

  • AI-assisted drafting — Customize every section with AI for your specific project scope.
  • Linked ITP — A matching inspection and test plan is generated alongside the method statement.
  • Multiple export formats — Download as a formatted PDF or editable Excel spreadsheet.
  • Editable starting point, not a final document — Review, verify, and adjust all content against your project requirements before use.

Static template vs. Quollnet workflow

FeatureStatic templateQuollnet
Project-specific contentManual fill-in requiredAI-assisted customization
Linked ITPSeparate document, no linkMatching ITP included
Export formatsUsually PDF onlyPDF and Excel
Structured sectionsFree-form layout13 standardized sections
Saved to your accountLocal file onlyCloud-saved, reusable
Content accuracyYou verify everythingAI-assisted, you still verify
CostOften free but time-intensiveFree to customize and download

What you can customize

When you save this method statement to your account, every section becomes editable. The following 13 sections are included:

  • Scope — Defines the activity and its boundaries.
  • References — Standards, specifications, and drawings.
  • Responsibilities — Roles and accountabilities.
  • Resources — Labour, plant, and equipment summary.
  • Materials — Materials and compliance requirements.
  • Equipment — Tools and equipment details.
  • Prerequisites — Hold points and pre-conditions.
  • Method sequence — Step-by-step construction sequence.
  • Safety controls — HSE risk controls and PPE.
  • Environmental controls — Environmental mitigation measures.
  • QA/QC — Quality inspection and test requirements.
  • ITP — Inspection and Test Plan table (has its own page).
  • Attachments — Referenced drawings and documentation.

Why this method statement is used

This method statement is used to define and communicate the approved procedure for carrying out method statement – installation of fire-rated doors and frames with certified hardware, smoke/intumescent seals, interfaces and testing on site. It ensures the work is planned in advance, the correct resources and controls are in place, and all personnel understand responsibilities, sequence, quality requirements, and safety controls before work begins. It aligns site execution with the documented scope and acceptance expectations.

Who uses this method statement

This method statement is used by contractors, site supervisors, project engineers, QA/QC engineers, HSE officers, consultants, and client representatives. It serves as a shared reference for planning, execution, supervision, inspection, and approval of the activity on site.

When it is prepared and submitted

The method statement is prepared before the work activity starts and submitted as part of the pre-construction documentation package for review and approval.

Who reviews or approves it

The method statement is usually submitted to the client representative, consultant, resident engineer, or project management consultant for review and approval before the work commences.

Important approval note

This method statement is an AI-assisted editable starting point, not a pre-approved document. Before use on any project, all content must be reviewed and approved by the relevant parties (superintendent, principal contractor, or client representative) in accordance with your contract and project quality plan.

For example: if your specification requires a departure from a referenced standard, that departure must be documented and approved separately — this method statement will not capture that automatically. Always verify against your applicable drawings, specifications, and regulatory requirements.

Method statement content

Scope

Overview

This method statement covers end-to-end installation of fire-rated door assemblies (timber or steel leaves and frames) including:
- Verification of approvals, labels, and product certification (UL/Intertek/CE/UKCA as applicable)
- Frame setting, anchorage, and plumb/level/square control
- Installation of leaves, certified ironmongery/door hardware (hinges, latches/locks, closers, panic hardware, hold-open devices)
- Installation of intumescent and smoke seals, drop/threshold seals, and fire-stopping at frame-to-wall interfaces strictly in accordance with tested details
- Coordination with passive fire protection works and fire alarm interfaces (where electromagnetic hold-opens or door monitoring are used)
- Functional checks, QA/QC inspections, ITP hold/witness points, as-built documentation, and authority (AHJ) compliance checks

Inclusions

  • Single and double leaf doors, with or without vision panels
  • Timber, steel, or composite frames compatible with the approved test evidence
  • Associated signage, door viewers (if permitted by certification), kick plates/edge guards (only if permitted by certification)
  • Finishes (paint/veneer) that do not compromise certification [Verify per project specifications]

Exclusions

  • Structural modifications to openings
  • Fire alarm system modifications beyond field testing of door hardware interfaces
  • Builder’s work in connection (unless specifically assigned)

Key Performance Criteria

  • Verified certification/labeling matches door schedule and fire strategy
  • Perimeter gaps to specified tolerances (see Method Sequence and ITP)
  • Correct, compatible hardware per the primary test evidence/assessment reports
  • Full continuity of smoke and intumescent seals without paint bridging
  • Perimeter fire-stopping compliant with tested details and FR of surrounding wall
  • Functional self-closing and latching from any opening angle permitted by design
  • Completion of ITP hold/witness points and close-out records ready for AHJ/Client handover.

References

Document TypeReference / NumberRevisionNotes
Standard EN 16034 / BS EN 16034
Standard BS EN 1634-1 / ISO 834 / NFPA 252 / ASTM E152 Regional equivalence acceptable [Verify per project specifications].
Standard BS EN 1634-3 / NFPA 105
Standard BS 8214
Standard EN 1935, EN 1154/1155, EN 12209, EN 1125/179, EN 1303
Standard BS EN 1366 / BS 476 / Primary test evidence
Project Docs Approved Shop Drawings / O&M / Door Schedule
Authority Local Code / AHJ [Verify per project HSE plan and local regulations].

Responsibilities

RoleResponsibilityName / Party
PM Project Manager Main Contractor
SE Site Engineer Main Contractor
QA/QC QA/QC Engineer Main Contractor
Installer Certified Fire Door Installer Specialist Subcontractor
Specialist Fire Stopping Specialist Specialist Subcontractor
HSE HSE Officer Main Contractor
E/FA Electrical/Fire Alarm Engineer MEP Subcontractor
AHJ Authority Having Jurisdiction (AHJ) Authority

Resources

Resource TypeDescriptionQuantityRemarks
Manpower 2–4 per team depending on door size/weight 2–4
Manpower 1–2 per team 1–2
Manpower Dedicated during hold/witness points 1
Manpower Setout and dimensional control 1

Materials

MaterialSpecification / GradeQuantityRemarks
Door leaf [Verify per project specs] As per schedule
Frame [Verify per project specs] As per schedule
Intumescent [Verify per project specs] Per door
Smoke seal [Verify per project specs] Per door
Ironmongery [Verify per project specs] Per door
Fire-stopping [Verify per project specs] Perimeter linear gap
Anchors/Shims [Verify per project specs] Per frame
Signs [Verify per project specs] Per door

Equipment

EquipmentCapacity / TypeQuantityInspection Required
Sets per team
As required
As required
Per QA/QC
As required

Prerequisites

  • Approvals: Submittals, shop drawings, hardware schedule, test evidence/assessment reports approved by the Engineer/AHJ.
  • Environmental: Storage 10–30°C, RH 40–60% for timber doors; acclimatize 48 h minimum before installation. Keep labels intact.
  • Openings: Wall/partition FR and construction verified; opening size, plumb, and level surveyed; substrate compressive strength and thickness confirmed for anchor selection.
  • Services: Utility/MEP clearance in partitions where drilling occurs; obtain Permit to Drill where required. [Verify per project HSE plan and local regulations]
  • Coordination: Confirm finished floor level/threshold details; ensure reinforcement/grounds in gypsum/metal stud walls installed; confirm door handing and swing.
  • Tools/Calibrations: Measuring devices and torque tools calibrated; inspection forms prepared.
  • HSE: Task-specific risk assessment and method statement (RAMS) briefed; permits (Work at Height, Drill/Hot Work if applicable) arranged.
  • Mock-Up (if required): Conduct and obtain approval before rolling works.

Method Sequence

StepActivityDescriptionResponsibilityInspection / Hold Point
1 Pre-installation verification Verify door schedule vs. labels; confirm rating, size, handing, hardware set, and compatibility to primary test evidence/assessment. Reject damaged or unlabeled products. QA/QC Engineer Document check
2 Survey openings Measure width/height at 3 points; check plumb/level and squareness; confirm wall FR and substrate suitable for anchors. Site Engineer Dimensional survey
3 Frame positioning and temporary fixing Assemble/sleeve frame if required; install non-combustible shims/packers; set frame to line and level with spreaders; avoid twist. Installer Visual and level check
4 Frame anchorage Drill and install anchors per manufacturer/test evidence. Typical spacing ≤600 mm c/c and within 150–250 mm from each corner/hinge zone. Maintain edge distances. Installer Hold Point – before concealment
5 Perimeter fire-stopping at frame/wall Install mineral wool backing (typ. 80–100 kg/m³) compressed ~10–20%; apply intumescent sealant both sides to required depth (e.g., 10–15 mm) as per tested detail; tag and record. Fire Stopping Specialist Hold Point – after prep, before closing finishes
6 Hang door leaves Fit intumescent hinge pads (if required); install hinges (typically 3 hinges per leaf > 44 mm thick or > 2.1 m height); check swing; avoid field trimming beyond allowance. Installer Witness Point
7 Install hardware (locks/latches/closers/panic/hold-open) Fix per hardware schedule and manufacturer templates; use specified screws; protect finishes; connect hold-open to FA system if applicable. Installer / Electrical Engineer Witness Point
8 Smoke and drop/threshold seals Fit continuous smoke seals around head/jambs; install drop seal; align for continuous contact without drag; no paint over. Installer Witness Point
9 Vision panels / glazing (if applicable) Install listed fire-resistant glazing and beads/intumescent liners per tested detail; set blocks/spacers as specified. Installer Witness Point
10 Signage and accessories Install mandatory signs both sides as required; accessories only if allowed by certification. Installer Visual check
11 Functional testing and adjustments Cycle doors (≥5–10 times); verify self-closing and latching; adjust closer speed/latching; confirm panic hardware; test hold-open release via fire alarm. QA/QC + Electrical Engineer Hold/Witness Point
12 Final QA, cleaning, and protection Remove debris; protect finished doors; compile as-builts and O&M; request AHJ/Engineer inspection for acceptance. QA/QC Engineer Final inspection

Health, Safety and Environment – Safety Controls

Task-Specific Hazards and Controls

  • Hazard: Struck-by/crush injury when hanging heavy door leaves
  • Likely consequence: Hand/foot injuries, musculoskeletal strain
  • Engineering/procedural control: Team lift with correct handling aids; use temporary door jacks/spreaders; set exclusion zone; sequence lifting with clear command
  • Required PPE: Safety boots with toe protection, cut-resistant gloves, long sleeves
  • Collective preventive measure: Use mechanical aids where feasible; keep floor clear of trip hazards
  • Inspection/permit/supervision: Supervisor present during hanging; pre-use inspection of lifting aids; toolbox talk

  • Hazard: Drilling into concealed services in partitions/walls

  • Likely consequence: Electric shock, flooding, service outage
  • Engineering/procedural control: Drawings review and cable/pipe detector scan; Permit to Drill; mark safe drilling zones
  • Required PPE: Insulated gloves (as required), safety glasses, hearing protection
  • Collective preventive measure: Lock-out/tag-out (where applicable); barriers and signage
  • Inspection/permit/supervision: Permit to Drill; Supervisor sign-off; records retained [Verify per project HSE plan and local regulations]

  • Hazard: Working at height (top hinge/closer installation)

  • Likely consequence: Falls from steps/podiums
  • Engineering/procedural control: Use podium steps with guardrails; maintain three points of contact; no overreaching
  • Required PPE: Non-slip footwear, fall-arrest only if MEWP used
  • Collective preventive measure: Task-specific Work at Height plan; spotter to foot the ladder if permitted
  • Inspection/permit/supervision: Pre-use inspection tags; Work at Height permit where required

  • Hazard: Power tool use and flying debris

  • Likely consequence: Eye injuries, lacerations, noise-induced hearing loss
  • Engineering/procedural control: Use guards, correct drill bits, dust extraction; maintain torque settings; keep both hands on tools
  • Required PPE: Safety glasses/face shield, hearing protection, gloves
  • Collective preventive measure: Designated cutting/drilling area; cord management
  • Inspection/permit/supervision: PAT testing (where required); supervisor spot checks

  • Hazard: Dust and silica from drilling masonry

  • Likely consequence: Respiratory irritation, long-term illness
  • Engineering/procedural control: On-tool extraction and wet suppression if feasible; limit drilling duration
  • Required PPE: FFP2/FFP3 (or N95/N99) respirator as required
  • Collective preventive measure: Ventilation; restrict access
  • Inspection/permit/supervision: Airborne dust checks (spot), HSE audits

  • Hazard: Chemical exposure (intumescent sealants/adhesives/PU foams)

  • Likely consequence: Skin/eye irritation, VOC exposure
  • Engineering/procedural control: Follow SDS; use low-VOC products where possible; avoid PU foam unless tested detail permits
  • Required PPE: Chemical-resistant gloves, safety glasses
  • Collective preventive measure: Local ventilation; spill kits
  • Inspection/permit/supervision: SDS available at point of use; COSHH assessment [Verify per project HSE plan and local regulations]

  • Hazard: Pinch points and sudden closer action

  • Likely consequence: Finger injuries
  • Engineering/procedural control: Keep hands away from hinge/closing edges; adjust closer speed gradually; signage during testing
  • Required PPE: Gloves, eye protection
  • Collective preventive measure: Exclusion zone during testing
  • Inspection/permit/supervision: Supervisor oversight during functional tests

  • Hazard: Fire alarm interface testing

  • Likely consequence: False alarms, uncontrolled releases
  • Engineering/procedural control: Coordinate with FM/Client; isolate zones as permitted; announce tests; restore settings post-test
  • Required PPE: Standard PPE
  • Collective preventive measure: Test plan and communication protocol
  • Inspection/permit/supervision: Permit-to-Test/Authorization by AHJ/Client

  • Hazard: Manual handling of frames and glass (vision panels)

  • Likely consequence: Strains, cuts, glass breakage
  • Engineering/procedural control: Use glass carrying aids and edge protection; correct lifting postures
  • Required PPE: Cut-resistant gloves, safety glasses
  • Collective preventive measure: Team lifts; clear route
  • Inspection/permit/supervision: Supervisor oversight; condition check of glass and protection prior to moving

[All controls to be verified per project HSE plan and local regulations.]

Environmental Controls

  • VOC and Odour Control: Use low-VOC sealants/adhesives where possible; ensure ventilation when applying intumescent products; keep containers closed.
  • Dust/Noise: Employ on-tool extraction and dampening; schedule noisy drilling during permitted hours; use acoustic barriers if required.
  • Waste Management: Segregate packaging (cardboard/plastic), metal offcuts, timber fragments, empty cartridges; dispose of chemical waste per SDS; no washout to drains.
  • Protection of Finishes: Use protective films on doors post-install; floor protection mats to prevent scratching during handling.
  • Storage/Handling: Store timber doors flat on level dunnage in dry conditions; avoid sunlight/heat that may warp leaves.
  • Spill Prevention: Keep spill kits; tray/liner under sealant/adhesive stations; immediate cleanup of drips.
  • Resource Efficiency: Pre-cut shims and fixings to reduce rework; verify openings to avoid abortive drilling.

Quality Assurance / Quality Control

Controls and Inspections

  • Verification: 100% label and certification check against door schedule prior to installation.
  • Calibration: Measuring tools, torque tools, pressure gauges calibrated; records maintained.
  • Dimensional Checks: Record plumb/level/square of frames; gap gauges for head/jamb/threshold per door.
  • Hardware Compatibility: Cross-check hardware sets with test evidence; no substitutions without Engineer/AHJ approval.
  • Fire-Stopping: Only tested/assessed perimeter systems; record material batch numbers and tag each opening where required.
  • Documentation: Maintain a unique Door ID with traceability to materials, installers, inspections, and photos.
  • Sampling/Frequency: 100% inspection at key hold/witness points; random re-check 10% post-completion to verify no drift.
  • Nonconformance: Raise NCR for damaged, relabeled, or modified doors outside permitted limits; agree remedial actions with manufacturer and Engineer.
  • Handover: ITP signed, as-builts, O&M manuals, warranties, training records; AHJ close-out where applicable.

Attachments

  • Approved shop drawings and door/hardware schedules
  • Primary fire test reports and assessment/extended application reports (e.g., EN 15269 series)
  • Manufacturer installation manuals and field modification limits
  • ITP forms: receipt/label check, frame set-out, gap gauge log, hardware torque log, seal continuity checklist, fire-stopping records
  • Calibration certificates for gauges/meters/torque tools
  • Risk assessments, method statements, and permits (Work at Height, Permit to Drill, Permit-to-Test fire alarm)
  • Material certificates: intumescent/sealants, mineral wool, anchors, hardware certifications
  • As-built records with Door ID matrix, photos, and AHJ inspection reports

This content is a read-only public reference. Download or customize to get an editable version.

ITP preview

The first inspection activities from the linked ITP for Method Statement – Installation of Fire-Rated Doors and Frames with Certified Hardware, Smoke/Intumescent Seals, Interfaces and Testing:

ActivityInspection / TestAcceptance CriteriaResponsibilityRecord
Materials receipt and label verificationCheck labels, ratings, sizes, handing against schedule; record serial numbers.100% match to approved submittals; labels intact and legible.QA/QC EngineerMaterial receipt/label log, photos
Openings survey and substrate verificationMeasure opening, plumb/level/square; verify substrate for anchors; confirm wall FR.Opening-to-frame clearance 10–20 mm [Verify]; plumb ≤3 mm/2 m; head level ≤3 mm.Site EngineerSurvey report
Frame positioning and anchorage (Hold Point)Verify shims/packers non-combustible; anchors type/spacing/torque; frame plumb/level/diagonals.Spacing ≤600 mm c/c and within 150–250 mm of corners; plumb ≤2 mm/1 m; diagonals ≤3 mm difference; torque per manufacturer [Verify].QA/QC + InstallerAnchor log, calibration certs, photos

Showing 3 of 10 inspection activities. View full ITP →

Related Inspection and Test Plan

An Inspection and Test Plan (ITP) is available for Method Statement – Installation of Fire-Rated Doors and Frames with Certified Hardware, Smoke/Intumescent Seals, Interfaces and Testing. The ITP defines the inspection activities, acceptance criteria, hold and witness points, responsible parties, and records required to verify the work described in this method statement.

View the Method Statement – Installation of Fire-Rated Doors and Frames with Certified Hardware, Smoke/Intumescent Seals, Interfaces and Testing ITP →

Frequently asked questions

Commonly referenced are BS EN 1634-1/-3, EN 16034, BS 8214, NFPA 80/105, and the manufacturer’s primary test and assessment reports. Verify local code and AHJ requirements.

Typical head/jamb gaps are 2–4 mm. Threshold gaps are ≤3 mm for smoke control with drop seals or ≤6–10 mm without, subject to the approved system and local code. [Verify per project specifications].

Only those explicitly permitted by the manufacturer’s installation manual and test/assessment reports. Unapproved drilling, cut-outs, or trimming invalidate certification.

Using materials and configurations proven by a tested/assessed system (e.g., mineral wool backing and intumescent mastic). Match the FR of the wall/door; record batch numbers and tag locations.

Cycle the door; verify self-closing and latching; check smoke/drop seal contact; test panic/escape hardware; and confirm electromagnetic hold-opens release on fire alarm.

Related resources