G
Guest

Method Statement: Testing and Commissioning of Lightning Protection System (LPS) inspection and test plan example.

Inspection and Test Plan for Method Statement: Testing and Commissioning of Lightning Protection System (LPS)

AI-assisted inspection and test plan connected to a method statement, with PDF and Excel export.

Published 19 Jun 2026 Rev. 00 2 views
About this ITP: This ITP defines inspections and tests for LPS commissioning, including air-terminal inspections, continuity and bonding checks, and earth resistance verification.

More than a static template

Unlike a downloadable Word or PDF template, this ITP is an AI-assisted editable starting point directly connected to its method statement. Every inspection activity, hold point, and acceptance criterion is structured and ready to adapt to your project.

  • AI-assisted customization — Tailor inspection activities and acceptance criteria to your specific project scope.
  • Linked method statement — This ITP is connected to the corresponding method statement describing the work sequence.
  • Multiple export formats — Download as a formatted PDF or editable Excel spreadsheet.
  • Editable starting point, not a final document — Review and verify all content against your project specifications and standards before use.

What you can customize

When you save this ITP to your account, every inspection row becomes editable. You can add, remove, or modify:

  • Inspection activity — Description of what is being inspected.
  • Inspection type — Hold point (H), Witness point (W), Review (R), or Monitor (M).
  • Responsibility — Contractor, subcontractor, engineer, or client.
  • Frequency — How often the inspection occurs.
  • Acceptance criteria — Referenced standard or specification requirement.
  • Records — Forms, test reports, or checklists required as evidence.

Why this ITP is used

To verify installed LPS complies with approved design and standards before handover, ensuring effective lightning risk mitigation.

Who uses this inspection and test plan

Contractor testing team, QA/QC, HSE, and Client/Consultant representatives for witnessing and acceptance.

When this ITP is prepared and submitted

After LPS installation and prior to handover; repeated when rectifying NCRs or during periodic maintenance tests.

Who receives or approves this ITP

Consultant/Client Representative for review, witnessing, and acceptance.

Inspection scope

Pre-commissioning review, access safety, air-termination, down conductor continuity, bonding to services, earth resistance, corrosion/mechanical protection, reinstatement, and documentation.

Typical hold, witness, and review points

Pre-test documentation review (Hold); Continuity tests (Hold); Earth resistance tests (Witness/Hold); Post-test reinstatement (Hold); Final acceptance (Hold).

Typical inspection records

Signed ITRs, test sheets with calibration references, photo logs, torque logs, site sketches of probe positions, NCRs/closeout, and completion certificate.

Important approval note

This ITP is an AI-assisted editable starting point, not a pre-approved document. Before use on any project, all inspection activities, hold points, and acceptance criteria must be reviewed and approved by the relevant parties (superintendent, principal contractor, or client representative) in accordance with your contract and project quality plan.

Always verify acceptance criteria against your applicable drawings, specifications, and regulatory requirements. Hold points must be confirmed with the relevant authority before work proceeds past that point.

Inspection and test plan

Activity Inspection / Test Acceptance Criteria Responsibility Record
Pre-commissioning Document Review Verify approvals, drawings, calibration, competencies All approvals current; instruments calibrated; team competent; risk assessment briefed QA/QC Engineer / Consultant ITR-01; Calibration list; TBT record
Access/WAH Setup Inspection Verify permits, edge protection/lifelines, exclusion zones PTWs valid; equipment tagged; rescue plan available HSE Officer / Consultant ITR-02; PTWs; WAH inspection tags
Air-Termination Visual Inspection Visual vs drawings; component conformity Conforms to approved layout; no damage/corrosion; correct fixings QA/QC Engineer / Consultant ITR-03; Photo log
Down Conductor Routing and Fixings Visual and torque check Routes per design; fixings spacing/torque per spec; labels present QA/QC Engineer / Consultant ITR-04; Torque log; Photos
Continuity Test of Down Conductors Low-resistance test per IEC 61557-4 End-to-end R ≤1.0 Ω or project value [Verify]; stable readings Testing Technician / Consultant ITR-05; Continuity test report
Equipotential Bonding Verification Visual + spot continuity checks All required bonds installed; R across bond ≤0.5 Ω [Verify]; correct clamp types; separation per design where applicable QA/QC Engineer / Consultant ITR-06; Bonding checklist
Earth Resistance Testing (3-pole) Fall-of-potential per IEEE 81/IEC 61557-5 Plateau verification (52/62/72% within ±5%); Resistance ≤ project requirement [Verify] Testing Technician / Consultant ITR-07; Earth test report; Site sketch
Alternative Clamp Test (if used) Clamp-on ground measurement Measured value ≤ project requirement [Verify]; method limitations noted Testing Technician / Consultant ITR-08; Clamp test report
Corrosion/Mechanical Protection Inspection Visual; coating checks No active corrosion; protection installed; coatings per spec [Verify] QA/QC Engineer / Consultant ITR-09; Photo log
Restoration and Labelling Verify all test links reconnected; torque; labels System fully restored; correct labeling and documentation Site Engineer / Consultant ITR-10; Reinstatement log
Final Documentation and Acceptance Review of dossier; outstanding NCRs closed Consultant acceptance and completion certificate issued Project Manager / Consultant ITR-11; Completion certificate; As-built set

This table is a read-only public reference. Download the PDF or Excel version, or customize this ITP to edit it for your project.

Frequently asked questions

They are defined in the method sequence and ITP. The Contractor gives 48–72 hours notice [Verify per contract] so the Consultant can attend.

Use the clamp-on method with all electrodes in place and document limitations; consider multiple measurement locations and correlation with historical data.

Yes, periodic inspections/testing intervals are set by the project O&M or standards (often annually or after major alterations). Verify the interval per contract.

Related method statement

This Inspection and Test Plan is associated with the Method Statement: Testing and Commissioning of Lightning Protection System (LPS) method statement, which describes the step-by-step construction sequence, resources, materials, equipment, safety controls, and environmental controls for this activity.

View the Method Statement: Testing and Commissioning of Lightning Protection System (LPS) method statement →

Related resources