G
Guest

Method Statement: HV Switching and Commissioning of RMU/Switchgear inspection and test plan example.

Inspection and Test Plan for Method Statement: HV Switching and Commissioning of RMU/Switchgear

AI-assisted inspection and test plan connected to a method statement, with PDF and Excel export.

Published 17 Aug 2026 Rev. 00 1 views
About this ITP: Defines Hold/Witness points, inspections, and acceptance criteria for RMU/switchgear commissioning, from permits and interlocks to primary injection and energisation.

More than a static template

Unlike a downloadable Word or PDF template, this ITP is an AI-assisted editable starting point directly connected to its method statement. Every inspection activity, hold point, and acceptance criterion is structured and ready to adapt to your project.

  • AI-assisted customization — Tailor inspection activities and acceptance criteria to your specific project scope.
  • Linked method statement — This ITP is connected to the corresponding method statement describing the work sequence.
  • Multiple export formats — Download as a formatted PDF or editable Excel spreadsheet.
  • Editable starting point, not a final document — Review and verify all content against your project specifications and standards before use.

What you can customize

When you save this ITP to your account, every inspection row becomes editable. You can add, remove, or modify:

  • Inspection activity — Description of what is being inspected.
  • Inspection type — Hold point (H), Witness point (W), Review (R), or Monitor (M).
  • Responsibility — Contractor, subcontractor, engineer, or client.
  • Frequency — How often the inspection occurs.
  • Acceptance criteria — Referenced standard or specification requirement.
  • Records — Forms, test reports, or checklists required as evidence.

Why this ITP is used

To ensure systematic, verified testing and safe energisation of HV RMU/switchgear in compliance with codes and project requirements.

Who uses this inspection and test plan

Contractor commissioning teams, HV Authorized Persons, Engineers/Consultants, and Utility/Authority representatives.

When this ITP is prepared and submitted

From pre-commissioning through post-energisation, culminating in handover.

Who receives or approves this ITP

The ITP is usually submitted to the client representative, consultant, resident engineer, or project management consultant for review and approval before the related work activity starts.

Inspection scope

Permits, mechanical/electrical integrity, IR/contact resistance, CT/VT, interlocks, relay settings, secondary/primary injection, SCADA SAT, phasing, energisation, post-energisation checks.

Typical hold, witness, and review points

Hold: relay settings approval, phasing, final pre-energisation, energisation. Witness: interlocks, secondary/primary injection, SCADA SAT, thermography.

Typical inspection records

PTW/LOTO logs, checklists, test reports (IR, ductor, CT/VT, injection), SCADA SAT sheets, settings files, phasing certificate, switching log, SOE, thermography, as-builts.

Important approval note

This ITP is an AI-assisted editable starting point, not a pre-approved document. Before use on any project, all inspection activities, hold points, and acceptance criteria must be reviewed and approved by the relevant parties (superintendent, principal contractor, or client representative) in accordance with your contract and project quality plan.

Always verify acceptance criteria against your applicable drawings, specifications, and regulatory requirements. Hold points must be confirmed with the relevant authority before work proceeds past that point.

Inspection and test plan

Activity Inspection / Test Acceptance Criteria Responsibility Record
Permits and pre-start briefing Review of PTW/SFT/LOTO Valid permits; LOTO applied; roles briefed and signed Contractor (AP), HSE; Engineer/Client (W) PTW/SFT forms; TBT record
Visual/mechanical inspection Checklist & torque verification No damage; torques per OEM; labels correct Contractor; Engineer (W) Pre-commissioning checklist; torque log
SF6 pressure and leak test (if applicable) Gauge reading & leak detection Pressure within OEM band; no leaks detected Contractor/OEM; Engineer (W) Gas log; leak test report
Earthing continuity Ductor test Bonding ≤0.05 Ω [Verify] Contractor; Engineer (W) Earthing test report
Insulation resistance (MV and control) IR at 5 kV (MV), 500–1000 V (control) MV ≥100 MΩ; control ≥5 MΩ [Verify] Contractor; Engineer (W) IR test sheets
Contact resistance Micro-ohm test 100 A Within OEM value; phase balance ≤20% Contractor; Engineer (W) Contact resistance report
CT/VT polarity and ratio Polarity/ratio tests Correct polarity; class accuracy per IEC 61869 Contractor (Protection); Engineer (W) CT/VT test reports
Interlock verification Functional demonstration All interlocks effective; no unsafe bypass Contractor/OEM; Engineer (W) Interlock checklist
DC system and TCS check Measurements and alarm tests Voltage within ±3%; TCS healthy Contractor; Engineer (W) DC system report
Relay settings approval Settings file review Matches approved coordination study; checksum logged Contractor; Engineer (H); Utility (W) Settings approval sheet
Secondary injection testing Secondary injection Pickup/time within specified tolerances Contractor (Protection); Engineer (W) Secondary injection reports
Primary injection testing Primary injection End-to-end trip proven at setpoints ±5% Contractor (Protection); Engineer (W) Primary injection reports
SCADA/RTU points and commands Point-to-point and command tests 100% correct indications/commands; time sync ±1 s Contractor (SCADA); Engineer/Client (W) SCADA SAT sheets
Intertripping and scheme logic Scheme trip tests Trips/blocks as per logic; transfer time ≤50 ms [Verify] Contractor; Engineer (W) Scheme test report
Phasing and rotation check Live phasing test Correct ABC sequence; safe to parallel Contractor (AP); Utility (H); Engineer (W) Phasing certificate
Final pre-energisation review Walkdown and checklist No open NCRs; area safe; interlocks locked Contractor; Engineer (H) Pre-energisation checklist
Energisation and initial load take-up Execution of switching program No abnormal alarms/trips; parameters within expected range Utility (H); Contractor (AP); Engineer (W) Switching log; SOE records
Post-energisation thermography Thermal scan No hotspots >15°C delta-phase or >70°C absolute [Verify] Contractor; Engineer (W) Thermography report
Handover dossier Document review Complete and approved test/setting/as-built pack Contractor; Engineer/Client (W) Handover approval

This table is a read-only public reference. Download the PDF or Excel version, or customize this ITP to edit it for your project.

Frequently asked questions

No. Primary injection validates the CT circuit end-to-end and is typically a required witness item unless expressly waived by the Engineer/Authority.

They are embedded in the ITP activities. Hold points require written release by the Engineer/Authority before progressing.

Project specifications and OEM limits prevail. Use the stricter requirement unless otherwise approved in writing.

Related method statement

This Inspection and Test Plan is associated with the Method Statement: HV Switching and Commissioning of RMU/Switchgear method statement, which describes the step-by-step construction sequence, resources, materials, equipment, safety controls, and environmental controls for this activity.

View the Method Statement: HV Switching and Commissioning of RMU/Switchgear method statement →

Related resources