G
Guest

Method Statement – Low-Current Floor Box and Data Outlet Installation inspection and test plan example.

Inspection and Test Plan for Method Statement – Low-Current Floor Box and Data Outlet Installation

AI-assisted inspection and test plan connected to a method statement, with PDF and Excel export.

Published 24 Jun 2026 Rev. 00 2 views
About this ITP: Defines hold/witness points and records for low-current floor box and data outlet installations, including certification testing and final acceptance.

More than a static template

Unlike a downloadable Word or PDF template, this ITP is an AI-assisted editable starting point directly connected to its method statement. Every inspection activity, hold point, and acceptance criterion is structured and ready to adapt to your project.

  • AI-assisted customization — Tailor inspection activities and acceptance criteria to your specific project scope.
  • Linked method statement — This ITP is connected to the corresponding method statement describing the work sequence.
  • Multiple export formats — Download as a formatted PDF or editable Excel spreadsheet.
  • Editable starting point, not a final document — Review and verify all content against your project specifications and standards before use.

What you can customize

When you save this ITP to your account, every inspection row becomes editable. You can add, remove, or modify:

  • Inspection activity — Description of what is being inspected.
  • Inspection type — Hold point (H), Witness point (W), Review (R), or Monitor (M).
  • Responsibility — Contractor, subcontractor, engineer, or client.
  • Frequency — How often the inspection occurs.
  • Acceptance criteria — Referenced standard or specification requirement.
  • Records — Forms, test reports, or checklists required as evidence.

Why this ITP is used

To ensure installations meet location, workmanship, segregation, and performance requirements prior to handover.

Who uses this inspection and test plan

Used by the contractor’s QA/QC team, site engineers, and the Client/Consultant for surveillance, witness, and acceptance.

When this ITP is prepared and submitted

Applied from pre-install coordination through final inspection and documentation closure.

Who receives or approves this ITP

Client/Consultant for review and acceptance per project procedure.

Inspection scope

Location checks, box installation, pathways, terminations, labeling, and 100% certification testing.

Typical hold, witness, and review points

Hold: location approval, floor box fixing, final acceptance. Witness: terminations and certification tests. Surveillance: conduit/cable pulls.

Typical inspection records

WIRs, checklists, photos, calibration certs, native tester results, as-builts, label registers, completion certificates.

Important approval note

This ITP is an AI-assisted editable starting point, not a pre-approved document. Before use on any project, all inspection activities, hold points, and acceptance criteria must be reviewed and approved by the relevant parties (superintendent, principal contractor, or client representative) in accordance with your contract and project quality plan.

Always verify acceptance criteria against your applicable drawings, specifications, and regulatory requirements. Hold points must be confirmed with the relevant authority before work proceeds past that point.

Inspection and test plan

Activity Inspection / Test Acceptance Criteria Responsibility Record
Pre-installation Coordination/Set-out Verify location vs. drawings; check obstructions; confirm separation strategy Locations marked within ±5 mm; conflict-free; hold point released Site Engineer / QA/QC / Consultant (Witness) WIR, marked-up drawings, photos
Floor Box Fixing (Raised floor or Screed) Level/flush check; compartment segregation; protection prior to pour (if screed) Flushness ±2 mm; secure fixing; segregation barriers in place; openings protected QA/QC (Witness) / Consultant (Hold) WIR, checklists, photos
Conduit/Pathway Inspection (Before Concealment) Bend count; fill factor; bushings/grommets; separations; bonding continuity (if metallic) Fill ≤40%; ≤2×90° bends; grommets fitted; separation per EN 50174-2/TIA-569-D; bonding continuous QA/QC (Witness) Concealed work inspection form, photos
Cable Pulling Check pulling methods, bend radii, lubricant usage (if any) No sheath damage; tension/bend limits maintained; correct cable IDs Supervisor (Surveillance) / QA/QC (Random) Daily pull log
Termination at Floor Box Color code; pair untwist; shield bond; torque; earthing continuity T568A/B as specified; untwist ≤13 mm; shield continuity; torque within spec; earth <0.5 Ω [Verify] QA/QC (Witness) Termination checklist, continuity record
Labeling and Records Verify TIA-606 scheme; end-to-end consistency Machine-printed durable labels; database/register updated QA/QC (Surveillance) Label schedule, register export
Certification Testing Field test to ISO/IEC 11801 Class E/EA or TIA Cat 6/6A using Level 2G tester 100% outlets PASS; Permanent Link ≤90 m or Channel ≤100 m; store native files QA/QC (Witness) / Consultant (Random witness) Tester native files + PDF/CSV, calibration cert
Final Inspection/Handover Visual checks; sample re-test; documentation completeness Defect-free installation; sample re-tests PASS; all records complete and approved QA/QC (Offer) / Consultant (Hold) Completion certificate, O&M, as-builts, warranties

This table is a read-only public reference. Download the PDF or Excel version, or customize this ITP to edit it for your project.

Frequently asked questions

Test the Permanent Link unless the specification requires Channel testing. Ensure test cords and adapters match the selected model.

For certification, 100% testing is standard. Sampling may be used only for verification during final inspection and does not replace full certification.

Related method statement

This Inspection and Test Plan is associated with the Method Statement – Low-Current Floor Box and Data Outlet Installation method statement, which describes the step-by-step construction sequence, resources, materials, equipment, safety controls, and environmental controls for this activity.

View the Method Statement – Low-Current Floor Box and Data Outlet Installation method statement →

Related resources