Method Statement: Lean Concrete Sub‑Base (LCB/DLC) for Rigid Pavements inspection and test plan example.

Inspection and Test Plan for Method Statement: Lean Concrete Sub‑Base (LCB/DLC) for Rigid Pavements

AI-assisted inspection and test plan connected to a method statement, with PDF and Excel export.

Published 23 Nov 2026 Rev. 00 2 views
About this ITP: This ITP defines inspections, tests, hold and witness points for lean concrete sub-base works. It ensures compliant delivery, placement, finishing, curing, and laboratory strength testing.

More than a static template

Unlike a downloadable Word or PDF template, this ITP is an AI-assisted editable starting point directly connected to its method statement. Every inspection activity, hold point, and acceptance criterion is structured and ready to adapt to your project.

  • AI-assisted customization — Tailor inspection activities and acceptance criteria to your specific project scope.
  • Linked method statement — This ITP is connected to the corresponding method statement describing the work sequence.
  • Multiple export formats — Download as a formatted PDF or editable Excel spreadsheet.
  • Editable starting point, not a final document — Review and verify all content against your project specifications and standards before use.

What you can customize

When you save this ITP to your account, every inspection row becomes editable. You can add, remove, or modify:

  • Inspection activity — Description of what is being inspected.
  • Inspection type — Hold point (H), Witness point (W), Review (R), or Monitor (M).
  • Responsibility — Contractor, subcontractor, engineer, or client.
  • Frequency — How often the inspection occurs.
  • Acceptance criteria — Referenced standard or specification requirement.
  • Records — Forms, test reports, or checklists required as evidence.

Why this ITP is used

To control and verify that lean concrete sub-base construction meets specified quality, geometry, finish, and strength requirements.

Who uses this inspection and test plan

QA/QC engineers, site engineers, laboratory staff, construction managers, and the Client/Engineer.

When this ITP is prepared and submitted

Implemented before, during, and after LCB placement—starting with material approvals through to final acceptance.

Who receives or approves this ITP

Engineer/Client Representative

Inspection scope

Covers materials approvals, batching, delivery checks, placement controls, vibration, levels, thickness, curing, bond breaker, and compressive strength testing.

Typical hold, witness, and review points

Pre-pour base/level check (Hold), bond breaker application (Hold/Witness), compressive strength sampling and testing (Witness), final acceptance (Hold).

Typical inspection records

Approved submittals, IRs, delivery tickets, fresh property logs, curing/bond-breaker application logs, strength test reports, thickness/level surveys, NCRs, acceptance certificate.

Important approval note

This ITP is an AI-assisted editable starting point, not a pre-approved document. Before use on any project, all inspection activities, hold points, and acceptance criteria must be reviewed and approved by the relevant parties (superintendent, principal contractor, or client representative) in accordance with your contract and project quality plan.

Always verify acceptance criteria against your applicable drawings, specifications, and regulatory requirements. Hold points must be confirmed with the relevant authority before work proceeds past that point.

Inspection and test plan

Activity Inspection / Test Acceptance Criteria Responsibility Record
Materials approvals COC/COA comply with referenced standards; approvals in place. QA/QC Engineer Approved submittals
Batch plant calibration Calibration current; tolerances within manufacturer/spec. QA/QC Engineer Calibration certificates
Pre-pour base and level check Base clean; moisture acceptable (no free water); levels within ±5 mm. Site Engineer Pre-pour IR, checklist
Concrete delivery verification Temp (ASTM C1064); Vebe/slump (BS EN 12350-3/ASTM C143); unit weight (ASTM C138) as scheduled Temp 5–32°C; Vebe 10–20 s or slump ≤25 mm; delivery ≤90 min. Lab Technician Field test reports; tickets
Placement and screed vibration Vibrator frequency check 4,000–7,000 vpm [Verify]; uniform head; no segregation/honeycomb. Paver Operator / QA/QC Equipment log; site diary
Surface regularity and level 3 m straightedge; level survey Straightedge ≤10 mm; level ±10 mm. Site Engineer / QA/QC QC checklist; survey file
Thickness verification Direct measure/cores +10/−5 mm; average ≥ design. QA/QC Engineer Thickness report
Curing application Visual, coverage confirmation Uniform membrane at 0.4–0.5 L/m², no holidays. Foreman / QA/QC Curing log
Bond breaker installation (if specified) Visual; film rate; overlap check Emulsion 0.3–0.5 kg/m² continuous; or PE sheet 125–200 µm with 150 mm overlapped and taped. Site Engineer / QA/QC IR; application log; photos
Compressive strength testing ASTM C31 (making/curing), ASTM C39 (testing) or EN 12390 Average ≥ f'c; no individual <0.85 f'c [Verify]. Lab Technician Lab test reports
Final acceptance and release Document review and walkdown All ITP items closed; NCRs resolved; records complete. Engineer / QA/QC Acceptance certificate

This table is a read-only public reference. Download the PDF or Excel version, or customize this ITP to edit it for your project.

Frequently asked questions

Follow project specifications. ASTM typically uses cylinders; BS EN uses cubes. Maintain consistency from trial mix to production.

At least every 25 m along each lane or one per 250 m² as a minimum, unless the project specifies a different frequency.

Only if an unbonded interface is specified in the contract. Otherwise, a smooth closed finish may suffice. Confirm with the Engineer.

Related method statement

This Inspection and Test Plan is associated with the Method Statement: Lean Concrete Sub‑Base (LCB/DLC) for Rigid Pavements method statement, which describes the step-by-step construction sequence, resources, materials, equipment, safety controls, and environmental controls for this activity.

View the Method Statement: Lean Concrete Sub‑Base (LCB/DLC) for Rigid Pavements method statement →